Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply

Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply
Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply
Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply
Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply
Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply

Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply

Maxgeek HAT520N Automatic Transfer Switch Controller Generator Set Dual Power Supply ATS Control Panel Description: -The powerful microprocessor contained within the HAT520N ATS controller allows for precision voltage (2-way 3-phase/single phase) measuring and make accurate judgment on abnormal voltage (power lost, over/under voltage, over/under frequency, loss of phase, phase sequence wrong) and control ATS to transfer after the delay has expired. This controller is suitable for NO Breaking ATS.

When 1# power is abnormal, the controller will send signal to start genset after the "1# abnormal delay" has expired. "Three remote" (remote control, remote measurement and remote communication). Function can be implemented with the help of LINK communication port.

Specification: Function Item: parameter Display: LED AC System: 1P2W/2P3W/3P4W Alternator Frequency: 50/60Hz Monitor Interface: LINK Programmable Interface: LINK Applicable Switch Type: no break position DC Supply: AC 170277V Case Dimensions (mm): 13912050 (LWH) Panel Cutout (mm): 130111 Operating Temperature: -25+70? Measure and display 2-way 3 phase voltage and frequency. Over/under voltage, loss of phase, phase sequence wrong, over/under frequency protection function. As default, phase sequence wrong protection and over/under frequency protection are disable; however, users can set the protection function as need.

Parameters can be set via PC software using SG72 module (USB to LINK) or other converse module. The voltage normal delay of 1# or 2# can be set in (0-60) seconds and the genset start delay can be set in (0-3600) seconds. The voltage abnormal delay of 1# or 2# can be set in (0-60) seconds and the genset stop delay can be set in (0-3600) seconds.

1# power priority, Auto/Manual, "No priority" and "2# power priority" can be set via controller front panel. Closing output signal can be set as on intervals or as continuous output.

Applicable for 2 isolated neutral line. In manual mode, ATS transfer 1# switch or 2# switch can be implemented via panel push button.

LED mounted on front panel can clearly show ATS running status. The output contact capacity of 1# and 2# power supply transfer relay (1# CLOSE, 2# CLOSE) is 16A AC250V, volts-free contact, can be directly used in driving switch to transfer. The output contact capacity of genset start relay (GENS START) is 7A AC250V/ 7A DC28V, volts-free N/C contact. Suitable for various AC systems (3 phase 4-wires, 2-phase 3-wires and single-phase 2-wire). Modular design, self extinguishing ABS plastic shell, pluggable terminal built-in mounting, compact structure with easy installation.

Package List: 1 x ATS Controller. Usually it cost about 35USD-50USD. If you receive defective item, please kindly notify us within 14 days.
Maxgeek HAT520N Automatic Transfer Switch Controller Generator Dual Power Supply